Specification
Product Name |
Air supply volume:m³/h |
Model |
Qty |
Use region |
Dehumidifier unit |
1300 |
JD-1300SCHX |
1set |
Liquid injection workshop |
Serial number |
Regional classification |
Constant temperature and humidity area |
|
1 |
Volume:m^3 |
75.3 |
|
2 |
Temperature and humidity requirements |
T=25±2℃ The dew point≤-40℃/-8℃ |
|
3 |
Purification level |
300000 level purification of return air |
|
4 |
Total wet load:g/h |
4100 |
|
5 |
Total heat load:W |
454 |
|
6 |
Design air volume |
1300 |
|
7 |
Design air change times |
21 |
|
8 |
Design dehumidification capacity(g/h) |
541.4 |
|
9 |
Designed heat removal(W) |
5000 |
|
10 |
Supply air temperature and dew point |
13℃/-65℃ |
|
11 |
Air volume: CMH |
Fresh air volume:CMH |
500 |
|
|
Dehumidification air volume of runner |
1400 |
Regenerated air volume:CMH |
500 |
||
Return air volume: CMH |
900 |
||
Air supply volume: CMH |
1300 |
||
Energy consumption of equipment |
KW |
Regenerative heating power: kw |
Before: 12/After:8 |
|
|
Power of regeneration fan:kw |
1.1 |
Power of treatment fan: kw |
2.05 |
||
Power of wheel drive motor:kw |
Before:0.025/After:0.025 |
||
Total summer power:kw |
24 |
Note:
Dehumidification unit is composed of primary effect filter section, front stage surface cooling section, runner dehumidification section, rear surface cooling section, blower section, regeneration system, control system and refrigeration system.