Dehumidification and Drying System Desiccant Dehumidifier

 Dehumidification and Drying System Desiccant Dehumidifier
 


Specification

Product Name

Air supply volume:m³/h

Model

Qty

Use

region

Dehumidifier unit

1300

JD-1300SCHX

1set

Liquid injection workshop

  

Serial number

Regional classification

Constant temperature and humidity area

1

Volume:m^3

75.3

2

Temperature and humidity requirements

T=25±2℃   

 The dew point≤-40℃/-8℃

3

Purification level

300000 level purification of return air

4

Total wet load:g/h

4100

5

Total heat load:W

454

6

Design air volume

1300

7

Design air change times

21

8

Design dehumidification capacity(g/h)

541.4

9

Designed heat removal(W)

5000

10

Supply air temperature and dew point

13℃/-65℃

11

Air volume: CMH

Fresh air volume:CMH

500

 

 

 

 

 

 

 

 

Dehumidification air volume of runner

1400

Regenerated air volume:CMH

500

Return air volume: CMH

900

Air supply volume: CMH

1300

Energy consumption of equipment

KW

Regenerative heating power: kw

Before: 12/After:8

 

 

 

 

 

 

 

 

Power of regeneration fan:kw

1.1

Power of treatment fan: kw

2.05

Power of wheel drive motor:kw

Before:0.025/After:0.025

Total summer power:kw

24

Note:

Dehumidification unit is composed of primary effect filter section, front stage surface cooling section, runner dehumidification section, rear surface cooling section, blower section, regeneration system, control system and refrigeration system.

INQUIRE